Before start-up

Confirm the installation is complete. Start-up begins once all six are in place.

  1. The MOAS cabinet is securely mounted in a ventilated location, close enough to the kitchen staff that they can hear its alarm.
  2. The 10-gallon solution container is securely mounted on the wall below the cabinet.
  3. The MOAS and exhaust fan field interlock is mounted and wired to both the exhaust fan and MOAS, and the 120 VAC, 20 A circuit dedicated to MOAS runs through it to the power switch on top of the cabinet.
  4. The 1/4 in copper cold-water supply is connected, and the building’s shutoff valve is open.
  5. Both nozzles are mounted in the exhaust duct where they can be reached for monthly maintenance.
  6. The black 3/8 in air line and the red 1/4 in solution line are connected to the couplings on top of the cabinet and to the tees that supply the nozzles, with equal lengths of tubing from each tee to its two nozzles.

Help on site

Stuck at the cabinet? Call us.

You work directly with the family business that builds the equipment.

  • Have the product, model and serial number ready.
  • Tell us which start-up step you are on and what you see.