Rev B · October 2026

PCU Installation, Operation & Maintenance Manual

Molitron Pollution Control Unit, models EPFA-24 through EPFA-144. For installing contractors, engineers, and the owners and staff who look after the unit day to day.

UL Certified · Safety US · MH45752 · Scan to view the UL listing

UL Listed · File MH45752

Models EPFA-24 through EPFA-144. Scan the QR code or select the mark to view Molitron’s listing with UL.

Listing scope
The Molitron PCU, EPFA-84, closed: a stainless enclosure with three access doors and the controls enclosure at the outlet end.
EPFA-84 shown, rendered from Molitron’s 3D model of the unit.

01

About this manual

Important

Installation must be performed by a qualified professional who has read and understands these instructions and is familiar with proper safety precautions. Read this manual before installing or servicing the equipment.

This manual belongs to the owner of the equipment and is needed for future maintenance. Leave it with the owner when installation or service is complete. The owner is responsible for maintaining and servicing the equipment.

What the PCU is

A UL Listed, fully welded 18-gauge stainless-steel enclosure that installs in the grease duct between the kitchen hood and the exhaust fan. Channels hold three rows of filters that remove particulate matter and grease vapor from kitchen exhaust. Removable doors give access to the filters and fire-protection components; a controls enclosure at the outlet end monitors system static pressure and drives a wall-mounted status panel.

The PCU with its three access doors removed: orange pre-filters behind the first door, green high-efficiency filters behind the second and third, and the controls enclosure at the outlet end.
  1. Inlet end, from the kitchen hood
  2. Pre-filters, MERV 9 (orange)
  3. High-efficiency filters, MERV 14 (green)
  4. High-efficiency filters, MERV 14, or optional carbon
  5. Static pressure controls enclosure

EPFA-84 with its access doors off, rendered from Molitron’s 3D model.

02

Models and filters

Every model is 63 in. long; the number is the width in inches. Airflow values are for planning.

ModelPlanning airflow, CFMWidthApprox. weightPre-filtersHigh-efficiency filtersCarbon adds
24 × 1224 × 2424 × 1224 × 24
EPFA-241,80024 in.250 lb–1–272 lb
EPFA-362,70036 in.350 lb1122108 lb
EPFA-483,60048 in.450 lb–2–4144 lb
EPFA-604,50060 in.550 lb1224180 lb
EPFA-725,40072 in.650 lb–3–6216 lb
EPFA-846,30084 in.750 lb1326252 lb
EPFA-967,20096 in.850 lb–4–8288 lb
EPFA-1088,100108 in.950 lb1428324 lb
EPFA-1209,000120 in.1,050 lb–5–10360 lb
EPFA-1329,900132 in.1,150 lb15210396 lb
EPFA-14410,800144 in.1,250 lb–6–12432 lb

Filter sizes are nominal, in inches. Units can be stacked to save floor space; contact Molitron.

Filter rows, inlet to outlet

  1. F1
    MERV 9 multi-pocket pre-filter (orange)23.31 × 23.31 × 12 in. (H × W × D)
  2. F2
    MERV 14 multi-pocket high-efficiency filter (green)23.31 × 23.31 × 12 in. (H × W × D)
  3. F3
    MERV 14 multi-pocket high-efficiency filter (green), or optional carbon filter23.31 × 23.31 × 12 in.; carbon 23.375 × 23.375 × 12 in. (H × W × D)

Half-size pre-filters and high-efficiency filters (24 × 12 nominal) are 23.31 × 11.31 × 12 in. (H × W × D). The filters sit in 1-in.-wide welded T304 channels (top, bottom and back side), sealed to the outer skin with high-temperature silicone.

03

Dimensions and construction

General arrangementMolitron PCU · all modelsDimensions in inches. Service side on the right, looking with the air flow.W is the model number in inches, drawn here at 36. Heights are not dimensioned.InletOutletF1F2F3Far sideService sideAir flow, inlet to outlet417172563131721W314314314128863WF1F2F341717256388WPlanService sideInlet endBack sideBottomInletOutletFar sideService sideOutletInlet12345678

163-inch length

Every model is 63 in. long in the direction of airflow. Width W is the model number: an EPFA-84 is 84 in. wide.

  1. 63-inch length. Every model is 63 in. long in the direction of airflow. Width W is the model number: an EPFA-84 is 84 in. wide.
  2. Filter channels. Welded 1-in. stainless channels hold the three filter rows. From the inlet end: F1 at 4 in., F2 17 in. further, F3 17 in. beyond that, then 25 in. to the outlet end.
  3. Access doors. Three removable 18-gauge stainless access doors, gasketed, on the service side. Doors on both sides are optional.
  4. Static pressure controls enclosure. At the outlet end, with a removable gasketed cover: the 120 VAC junction box and 120/24 VAC transformer, the static pressure gauge, two pressure switches and the wiring terminal block.
  5. Duct flange. A 1.5-in. flange around the full perimeter of each end, for welding to the connecting ductwork (by others).
  6. Hanger angles. An 11-gauge stainless hanger angle welded at each top corner, with a 1/2-13 threaded hole. Its removable galvanized eyebolt (1/2-13, 1-7/8 in. thread) is for lifting and positioning only. Hang the unit on spring hangers with separate upper and lower threaded rods; the hangers, rods and hardware are by others, and the project’s designer or installer selects the rod size, the hangers’ rated load and the anchorage.
  7. Bottom rails. Two full-width stainless T304 channels, 1.5 × 4 in. with 1/8-in. wall, welded to the bottom 8 in. in from each end.
  8. Cleaning drains. Three 1-1/2 in. stainless FPT couplings in the bottom, 13, 30 and 51 in. from the inlet end, as dimensioned in the plan. Connect them to a common 2-1/2 in. drain routed to the grease interceptor (by others).
Common to every model: the 63-in. length; the positions along it of the filter channels, access doors, controls bay, drains and bottom rails; and the 1.5-in. end flanges. Model-specific: the width W, which is the model number in inches, and the filters across it. Not dimensioned here, or set by the project, so confirm them on the project’s submittal drawing: the heights, the controls enclosure, the fire-suppression pre-piping, the electrical and drain connections, and the connecting ductwork (by others).

04

Installation

30 in. service space18 in.*18 in.*18 in.*Access doorsAir flow →inlet to outlet
Plan view, to scale. Keep 30 in. free in front of the access doors. *18 in. to combustible materials and building insulation, or zero clearance to noncombustible materials.
Location
In the grease duct between the kitchen hood and the exhaust fan, indoors or outdoors, in an accessible location.
Direction
Inlet end from the kitchen, outlet end toward the exhaust fan.
Duct connections
Welded to the exhaust duct at each end, using the 1.5-in. perimeter flange.
Inlet duct
Provide straight duct on the inlet side of at least 3 times the duct diameter, to avoid system effect.
Exhaust fan
UL Listed for kitchen exhaust, backward-inclined utility type, with easily adjustable RPM. The PCU’s initial (clean-filter) resistance is 1.54 in. w.g.; size the fan for 2.5 in. w.g. plus hood and duct static losses.
Rooftop support
The two 4-in. stainless bottom channels support the unit across its full width. The installing contractor provides a code-approved roof curb.
Indoor suspension
Suspend the unit from its four hanger angles on spring hangers, with separate upper and lower threaded rods; the hangers, rods and hardware are by others. The project’s designer or installer selects the rod size, the hangers’ rated load and the anchorage. The removable eyebolts are for lifting and positioning only, not for hanging the unit.
Service side
At least 30 in. of free space between the access doors and any adjacent wall.
Other sides
At least 18 in. to combustible materials and building insulation, or zero clearance to noncombustible materials.
Above a ceiling
A permanent platform (by others) is required for servicing every four weeks, at the same height as the bottom of the unit.
Drains
Connect the three 1-1/2 in. cleaning drains to a common 2-1/2 in. drain and route it to the grease interceptor (by others).
Codes
Install and use only in accordance with these instructions. The installing contractor is responsible for local code requirements.

05

Fire protection

Molitron provides fire-suppression pre-piping: the PCU comes piped to its fire-suppression nozzles, ready for the fire-protection installer to connect. ANSUL is one brand option, and other customer-selected brands are supported.

The PCU does not connect to the building sprinkler system.

Fire-suppression design and approval are project-specific. Confirm the pre-piping on the project’s submittal drawing.

The PCU from above with its top cut away and its filters faded: red pre-piped risers rise along both side walls in the spaces before, between and after the filter rows, each ending in a capped nozzle fitting.

The pre-piping in red, with the top cut away, the doors off and the filters faded back. Rendered from Molitron’s 3D model of the EPFA-84; the pipework is illustrative.

Field responsibilities
The fire-protection installer is responsible for the final hook-up, permits, drawing submittals and final testing, and provides the tanks, agent, piping from the tanks to the pre-piped nozzles, regulated actuators, cartridges and related components.
Detection
The detectors are mechanical fusible links, not electric.

06

Controls, wiring and status panel

Danger: risk of electric shock

Disconnect power before servicing. The junction box in the controls enclosure carries 120 VAC.

Static pressure controls enclosure

At the outlet end of the unit, behind a removable gasketed cover. A 120 VAC supply from the building electrical panel (by others) enters a junction box and powers a 120/24 VAC transformer. Everything after the transformer runs at 24 VAC.

High static switch adjustment
The ringed hole in the instruction label, over switch E’s brass adjusting port.
Static pressure gauge
Shows total system static pressure, 0 to 10 in. w.g.
Wiring terminal block
The field cable to the status panel lands on the top of the block: 1 Common (white), 2 Black (green light), 3 Red (red light). The bottom takes the factory wiring from the switches.
Fan-on air switch
Closes when static pressure reaches 1.5 in. w.g., and the green light turns on.
High static pressure air switch
Fed through switch D. Closes when static pressure reaches its setting, and the red light starts blinking beside the green.
Inside the controls enclosure: the transformer at the top, gauge B below it, terminal block C to the right, the test lamp at the left, and the instruction label with hole A over switch E.

The controls enclosure with its cover off. Molitron provides the 24 VAC test lamp and an Allen wrench for setting switch E.

The 120/24 VAC transformer on the junction box, with its two 24 VAC leads.
Junction box and transformer120 VAC in from the building panel; 24 VAC out to the switches and lights.
The static pressure gauge, reading 0 to 10 inches water column.
Static pressure gaugeTotal system static pressure, 0 to 10 in. w.g.
The three-position terminal block: the field cable’s white, black and red wires on top, the factory wiring below.
Terminal block1 Common, 2 Black, 3 Red: the field cable to the status panel lands on top; the factory wiring enters below.
The instruction label’s ringed hole over the high static switch, below the test lamp.
Adjustment holeThe ringed hole over switch E’s port, below the test lamp.
The instrument panel drawn transparent to show the two air switches behind it, one above the other.

The instrument panel and its label shown clear: fan-on switch D below, high static switch E above, its brass adjusting port behind hole A.

Wiring

One 3-wire 18-gauge plenum cable runs from terminal block C to the status panel, terminal for terminal. The cable, the 120 VAC supply and their connections are by others.

TerminalWireAt the status panel
1 · Common WhiteCommon to both lights
2 · Green light BlackGreen light: exhaust fan on
3 · Red light RedRed light, through the flasher: service required

Switch E is fed through switch D, so the red light can only come on while the exhaust fan is running.

PCU controls wiringA 120 VAC supply from the building electrical panel, by others, feeds the junction box and 120/24 VAC transformer in the static pressure controls enclosure. The transformer’s 24 VAC side feeds fan-on switch D. D feeds terminal 2 and, through a jumper, high static switch E, which feeds terminal 3. Terminal 1 is Common. A 3-wire 18-gauge plenum cable, by others, runs terminal for terminal to the status panel: white to Common, black to the green light, red through a flasher to the red light.Static pressure controls enclosureStatus panelBuilding electricalpanel120 VACby othersJunction box +120/24 V transformerD · fan-on switchcloses at 1.5 in. w.g.E · high static switchcloses at its setting11white · Common22black · green light33red · red lightC · terminalsfield cable on top3-wire 18 GAplenum cableby othersGreen lightFlasherRed lightFactory-wired
  • White, terminal 1: Common
  • Black, terminal 2: green light
  • Red, terminal 3: red light
  • Factory wiring
  • 120 VAC supply

Fan on. The exhaust fan builds static pressure past 1.5 in. w.g. and switch D closes: the fan is on. 24 VAC reaches terminal 2 and the green light comes on. D also feeds switch E.

Status panel and its lights

The Molitron Enviro-Pak Filter Status Panel: a factory-furnished, factory-wired stainless enclosure, 12 in. wide, 8 in. high and 2-5/8 in. deep, with a green and a red light. Terminals 1, 2 and 3 on its back match terminal block C. A flasher inside makes the red light blink. Mount it indoors where it can be watched every day; the kitchen or an office is suggested.

The status panel with both lights off.

Both lights off: the exhaust fan is off.

With the fan off, switch D is open and neither light has power.

The status panel with its green light on.

Green light: the exhaust fan is on.

Normal running. Nothing to do but keep to the four-week filter inspection.

The status panel with its green light on and its red light blinking.

Green and blinking red: service is needed now.

Static pressure has reached switch E’s setting. Inspect every filter and replace any that are loaded with grease and restricting airflow.

The open back of the status panel: a three-position terminal block with its blue identification label, the green and red light holders, and the flasher.

The back of the status panel, from Molitron’s 3D model.

Green light: the exhaust fan is on.

Normal running. Nothing to do but keep to the four-week filter inspection.

Green: the exhaust fan is on. Green and blinking red: service is needed now; inspect the filters and replace those loaded with grease. Both off: the fan is off.

The red light can blink only while the green light shows the fan is on: switch E is fed through switch D.

07

Setting the pressure switch

Set high static pressure switch E after system start-up and after air balance is complete. Molitron provides the tools: one 24 VAC panel test lamp and one Allen wrench. Letters and terminal numbers are those of section 06.

The test lamp lit just below gauge B, its leads on the top of terminals 3 and 1 of terminal block C, with the red field wire bent aside.
An illustration: the gauge positions are examples, not readings or settings for your system, and the time-lapse does not forecast how long filters last.

Step 1 of 4

Connect the test lamp

After start-up and air balance, loosen the top of terminal 3 on block C and disconnect the red field wire. Connect one lead of the 24 VAC test lamp to the top of terminal 3 and the other to the top of terminal 1 (Common), beside the white field wire, and tighten both. The lamp lights. Leave it where you can see it and gauge B together.

  1. Connect the test lamp. After start-up and air balance, loosen the top of terminal 3 on block C and disconnect the red field wire. Connect one lead of the 24 VAC test lamp to the top of terminal 3 and the other to the top of terminal 1 (Common), beside the white field wire, and tighten both. The lamp lights. Leave it where you can see it and gauge B together.
  2. Find the clean-filter reading. Insert the Allen wrench through hole A into the brass port on the front of high static switch E. Turn it slowly clockwise until the lamp goes out. Note the reading on gauge B: the static pressure with clean filters. Write it in the record for this unit.
  3. Add 1.5 turns. Turn the wrench a further 1.5 turns clockwise. The lamp stays out. Remove the test lamp, reconnect the red field wire to the top of terminal 3 and tighten it, then put the lamp and the wrench back on the shipping terminal.
  4. Simulate weeks of cooking. In service, the green light shows the fan is on. As cooking loads the filters, static pressure on gauge B rises; when it reaches switch E’s setting, the red light blinks beside the green. Inspect the filters then, and replace those that need it. The time-lapse is an illustration: how quickly filters load depends on the kitchen.

08

Maintenance

Every four weeks

Inspect and service the filters, and replace any that are loaded with grease and restricting airflow. A blinking red light means service is needed now, whatever the date. Record each visit in the filter service log (section 10).

The PCU with its doors off and an orange pre-filter slid part way out of the first row toward the service side.

With the doors off, each filter slides out of its channels toward the service side. EPFA-84 shown, with an F1 pre-filter part way out.

Step 1 of 6

Open the doors

Remove the access doors on the service side.

  1. Open the doors. Remove the access doors on the service side.
  2. Remove used filters. Slide out the filters that are loaded with grease and restricting airflow. Steam-clean the interior if grease has built up.
  3. Check the gaskets. Each filter takes a 1/4-in. closed-cell neoprene gasket on one vertical side. Green high-efficiency filters come with it fitted; add it to orange pre-filters and to any carbon filter without one. Only one gasket goes between filters: never add a second.
  4. Install in order. From the inlet: orange pre-filters (MERV 9) in the first row, green high-efficiency filters (MERV 14) in the second, and green high-efficiency filters (MERV 14) or optional carbon filters in the third.
  5. Push each one home. Push each filter individually into the upper and lower channels, gasketed side first, toward the wall opposite the doors: the first filter’s gasket seals against that wall, and each filter after it seals against the bare side of the one before, one shared seal per joint.
  6. Close up tight. The last filter’s door-side vertical edge is exposed: add gasket there as needed so the row is tight when the door closes. The damper shields seal the top and bottom of each row. Then seat the doors against their gaskets.

Replacement filters

The owner or the owner’s representative replaces used filters as often as required. Use new filters of the same quality and manufacturer as the original equipment. Molitron accepts no responsibility for visible contaminants escaping the PCU if replacement filters do not match the original specifications or are not installed as described here. Order replacement filters from Molitron: 303-969-8888 · cleanair@molitron.com.

Cleaning

Steam-clean the inside of the PCU to remove any grease buildup.

09

Warranty

The PCU and its component parts, the static pressure controls enclosure and the status panel, are warranted to be free from defects in material and workmanship for 12 months from the date of shipment.

What’s covered
A part that proves defective within 12 months is, after examination by the factory, repaired or replaced at no charge for parts. Labor, including installing the replacement part, is not included. Molitron does not accept returns of Molitron products.
Not covered
Parts damaged by the freight carrier between the factory and the destination, or by the installing contractor. The factory is not liable for incidental or consequential losses attributable to malfunctioning equipment.
The warranty does not apply if
  • The PCU is not installed by a qualified installer per the factory instructions.
  • The PCU is not installed to federal, state and local codes.
  • The PCU is misused or neglected.
  • The PCU is operated outside its published capacity.
  • The invoice is not paid within the terms of the sales agreement.

The warranty is activated once the owner’s acknowledgement (section 10) is signed and returned to the factory. Email a signed copy to cleanair@molitron.com.

10

Start-up and owner forms

Fill these in on screen, then print them or save them as PDF. Nothing you type leaves your browser.

Installing contractor’s checkoff list

Complete this list before the factory representative starts up the unit. Installation must follow this manual.

0 of 8 checked

Warranty: follow the maintenance instructions in this manual to keep the 12-month manufacturer’s warranty.

Record for this unit

Fill this in at start-up and leave a copy with the owner, so whoever services the unit later has its details in one place.

Owner’s acknowledgement of required maintenance

I have read the required maintenance instructions for the Molitron PCU and accept full responsibility for maintaining the equipment in accordance with them, with the full knowledge that if it is not adequately and properly maintained, it will not satisfactorily perform its intended purpose and the warranty will be void.

The warranty is activated when this acknowledgement is signed and returned to Molitron: cleanair@molitron.com.

Filter service log

Record each four-week inspection and every filter change, ticking each bank replaced. Keep it with this manual.

DateFilters replacedServiced byNotes
F1F2F3

Printed, the log has 13 lines: a year of four-week inspections.

11

Engineer’s corner

Copy-ready text for a project specification, written from this manual. Edit the model for your project.

PCU — Kitchen exhaust pollution control unit

1. Manufacturer: Molitron Company Inc. Pollution Control Unit (PCU), Model EPFA-[24|36|48|60|72|84|96|108|120|132|144].
2. Listing: UL Listed under File MH45752, investigated to UL 8782, Outline of Investigation for Pollution Control Units for Commercial Cooking Operations.
3. Enclosure: 18-gauge Type 304 stainless steel, fully welded, 63 in. long by model width; 1.5-in. perimeter flange at each end for welded duct connection; full-width sloped top panel; two full-width T304 stainless bottom channels, 1.5 x 4 in.
4. Access: three removable, gasketed 18-gauge stainless access doors on the service side (doors both sides optional).
5. Filtration, in airflow order: F1 MERV 9 multi-pocket pre-filters; F2 MERV 14 multi-pocket high-efficiency filters; F3 MERV 14 multi-pocket high-efficiency filters, or carbon filters where odor treatment is required.
6. Fire protection: factory fire-suppression pre-piping to nozzles, for connection by the fire-protection installer to an ANSUL or other customer-selected system (mechanical fusible-link detectors). A building sprinkler connection is not provided.
7. Drains: three 1-1/2 in. stainless FPT cleaning drain couplings.
8. Monitoring: static pressure controls enclosure with gauge, fan-on and adjustable high static pressure switches, 120/24 VAC transformer; wall-mounted stainless status panel (green: exhaust on; blinking red: service required).
9. Electrical: 120 VAC supply to the unit (by others); 3-wire 18-gauge plenum cable from unit to status panel (by others).
10. Clearances: 30 in. on the service side; 18 in. to combustibles and building insulation on other sides, or zero to noncombustible materials.
11. Exhaust fan (by others): UL Listed for kitchen exhaust, backward-inclined utility type with adjustable RPM. Initial PCU resistance 1.54 in. w.g.; size the fan for 2.5 in. w.g. plus hood and duct static losses.

Listing details: equipment listings. For drawings or project questions, contact Molitron.